RCBO- RNC1-40

| Application 


Electromagnetic RCBO RNC1-40, with more reliable perfor mance, meets any requirement for protection against residual current, overload and short circuit for all household, commercial and PV low voltage distribution systems.It is easy to be assembled and works with the same series of compact circuit breakers together. .


| Features


· Only 36mm for 1P+N/2P and 72mm for 3P/3P+N/4P

· Protection against residual current, overload, short circuit and  arc faulty

· Rated breaking capacity: 6kA

· Rated current: 6/10/13/16/20/25/32/40A

· Input and output reverse available

Technical Data

| Electrical 


·Standard: IEC/EN 61009-1

IEC 62423

IEC 62606

·Rated short-circuit breaking capacity Inc: 6kA

·Residual current operating characteristic: 

Type A, Type A[S], Type A[G]

Type B, Type B[S], Type B[G]

MCB+AFDD

Type A+AFDD, Type B+AFDD

·Number of poles: 1P+N, 2P, 3P, 3P+N, 4P

·Rated current In: 6~40A

·Rated residual operating current l△n(mA): 10, 30, 100, 300mA

·Rated residual non-operating current(mA): 0.5 I△n

·Trippping curve: B/C/D

·Rated voltage Un: 240/415V AC

·Rated frequency: 50/60 Hz

·Rated impulse withstand voltage Uimp: 4kV

·Electrical life: 4000



| Mechanical


·Frame size: 45mm

·Device height: 77mm

·Device width: 36mm(1P+N/2P), 72mm(3P/3P+N/4P)

·Installation: Quick fastening on 35mm DIN rail

·Mechanical life: 10000

·Upper and lower terminals: Open mouthed/lift terminals

·Terminal protection: Finger and hand touch safe

·Terminal capacity: 1~6mm²

·Terminal fastening torque: 1.2Nm

·Degree of protection: IP20

·Operating temperature: -25℃~+40℃







Dimensions(mm)
Specification
Connection Diagrams