搜索
PRODUCT
PRODUCT CENTER
RNC1-40E-RCBO

| Application


RCBO RNC1-40E meets any requirement for protection against residual current, overload and short circuit for all household, commercial and PV low voltage distribution systems. It is easy to be assembled and works with the same series of compact circuit breakers together.




| Features


· Only 18mm for 1P+N and 36mm for 2P+2N

· Protection against residual current, overload and short circuit

· Rated breaking capavcity: 6kA

· Rated current: 6/10/13/16/20/25/32/40A

· Input and output reverse available

Technical Data

| Electrical 


·Standard: IEC/EN 61009-1

·Rated short-curcuit breaking capacity Inc: 6kA

·Residual current operating characteristic: AC and A Type

·Number of poles: 1P+N, 2P+2N

·Rated current In: 6~40A

·Rated residual operating current l△n(mA): 10, 30, 100, 300mA

·Rated residual non-operating current(mA): 0.5 I△n

·Trippping curve: B/C

·Rated voltage Un: 240VAC

·Rated frequency: 50/60Hz

·Rated impulse withstand voltage Uimp: 6kV

·Electrical life: 4000


| Mechanical


·Frame size: 45mm

·Device height: 77mm

·Device width: 18mm(1P+N), 36mm(2P+2N)

·Installation: Quick fastening on 35mm DIN rail

·Mechanical life: 10000

·Upper and lower terminals: Open mouthed/lift terminals

·Terminal protection: Finger and hand touch safe

·Terminal capacity: 1~10mm²

·Terminal fastening torque: 1.2Nm

·Degree of protection: IP20

·Operating temperature: -25℃ ~ +40℃




Dimensions(mm)
Specification
Connection Diagrams
Associated product column