| Features
· Compatible with standard busbar.
· Twin-purpose terminal (lift/open-mouthed) above and below.
· Busbar positioning optionally above or below.
· Meets the requirements of insulation co-ordination.
· For overload & short circuit protection which used in household and industrialdistribution system.
| Electrical ·Standard :IEC/EN 60947-2 ·Rated short -circuit current Inc: 10kA ·Number of poles: 1P, 2P, 3P, 4P ·Rated current In: 10-125A ·Triping curve: B\C\D ·Rated voltage Un: 230/415VAC ·Rated frequency: 50/60Hz ·Energy limiting class: 3 ·Electrical life: 1500(In=10-100A) 1000(In=125A) | | Mechanical ·Frame size: 45mm ·Device height: 71mm ·Device width: 27mm (1.5MU) ·Installation: Quick fastening on 35mm Din rail ·Mechanical life: 8000(In=10-100A), 7000(In=125A) ·Upper and lower terminals: Open mouthed /lift teminals ·Terminal protection: Finger and hand touch safe ·Terminal capacity: 1-50mm² ·Terminal fastening torque: 2.0Nm ·Degree of protection: IP20 ·Operating temperature: -25℃ ~ +40℃ |